Common Structures and Heat Dissipation Designs in Custom Liquid Cold Plates
Time:
2025-08-13
source:
Liquid cold plates, as an efficient thermal management solution, are widely used in data center servers, electric vehicle battery packs, photovoltaic inverters, and high-power electronic equipment. Because heat dissipation requirements vary significantly across applications, the structure and heat dissipation design often become key factors influencing performance and cost when customizing liquid cold plates.
First, in terms of structure type, common liquid cold plates include embedded tubes, welded tubes, extruded tubes, and integrally machined tubes.
Embedded tubes feature coils embedded within aluminum or copper plates, where fluid flows to remove heat. This structure offers low manufacturing costs and is suitable for medium heat dissipation requirements, but the heat transfer path is relatively long.

Welded plates typically utilize friction stir welding or brazing to weld upper and lower plates with flow channels into a single unit. This results in a compact structure and high thermal efficiency, making it suitable for high-power density equipment.
Extruded plates utilize profile extrusion to create internal flow channels, making them suitable for mass production and offering a good balance between cost and performance.
Monolithic Liquid Cold Plates utilize CNC precision machining to create flow channels directly within the plate. This offers high precision and flexibility, but the manufacturing cost is relatively high, and they are primarily used in high-end equipment.
Secondly, flow channel layout is crucial in heat dissipation design. Common designs include straight-through, serpentine, parallel-flow, and microchannel.
Straight-through channels offer low resistance and stable flow rates, making them suitable for systems requiring low pressure drop.
Serpentine channels increase the contact area between the liquid and the heat exchange surface, improving heat dissipation efficiency, but also result in a higher pressure drop.
Parallel-flow designs evenly distribute flow and avoid localized overheating, making them suitable for equipment with multiple heat sources.
Microchannel structures offer a higher heat transfer coefficient per unit area, making them ideal for heat dissipation at extreme power densities. However, they place high demands on processing technology and fluid cleanliness.
In addition, customizing Liquid Cold Plates requires a comprehensive consideration of material thermal conductivity, corrosion resistance, weight, and cost. Aluminum alloy is most widely used due to its light weight and reasonable cost, while copper and copper alloys are used in applications requiring higher thermal conductivity.
The structural type and heat dissipation design of a Liquid Cold Plate require a comprehensive balance between the device's power density, installation space, coolant type, and budget. A well-chosen structural design and a rational flow path layout ensure optimal balance between manufacturing cost and operational efficiency while ensuring heat dissipation performance.